SEMEM_ZQ-20型軸流暖風機用于候車室、體育館等
軸流暖風機性能參數(shù) :
型 號 | 風 量(m3/h) | 蒸氣壓力 ( ℃ ) | 散熱量 ( kw ) | 凝結(jié)水量 ( kg/h ) | 進口溫度 ( ℃ ) | 出口溫度 ( ℃ ) | 噪 音 dB(A) | 風 速 ( m/s ) |
ZQ-20 | 2000 | 0.1 | 18.18 | 29.7 | 15 | 42 | 60 | 3.05 |
0.2 | 19.53 | 32.34 | 44 | |||||
0.3 | 20.87 | 35.03 | 46 | |||||
0.4 | 22.22 | 37.84 | 48 | |||||
ZQ-30 | 3000 | 0.1 | 30.3 | 49.51 | 15 | 45 | 60 | 3.2 |
0.2 | 33.33 | 55.19 | 48 | |||||
0.3 | 36.36 | 61.02 | 51 | |||||
0.4 | 38.38 | 65.36 | 53 | |||||
ZQ-40 | 4000 | 0.1 | 36.36 | 59.41 | 15 | 42 | 65 | 3.03 |
0.2 | 39.05 | 64.66 | 44 | |||||
0.3 | 41.75 | 70.07 | 46 | |||||
0.4 | 44.44 | 75.68 | 48 | |||||
ZQ-50 | 5000 | 0.1 | 50.5 | 82.52 | 15 | 45 | 65 | 3.45 |
0.2 | 55.5 | 91.99 | 48 | |||||
0.3 | 60.6 | 101.71 | 51 | |||||
0.4 | 63.96 | 108.92 | 53 | |||||
ZQ-60 | 6000 | 0.1 | 54.54 | 89.12 | 15 | 42 | 65 | 3.44 |
0.2 | 58.58 | 96.94 | 44 | |||||
0.3 | 62.62 | 105.09 | 46 | |||||
0.4 | 66.66 | 113.17 | 48 | |||||
ZQ-70 | 7000 | 0.1 | 63.63 | 103.98 | 15 | 42 | 70 | 3.56 |
0.2 | 68.34 | 113.17 | 44 | |||||
0.3 | 73.05 | 122.6 | 46 | |||||
0.4 | 77.77 | 132.44 | 48 | |||||
ZQ-80 | 8000 | 0.1 | 72.77 | 118.92 | 15 | 42 | 70 | 3.79 |
0.2 | 80.8 | 133.79 | 45 | |||||
0.3 | 88.88 | 149.17 | 48 | |||||
0.4 | 91.57 | 155.94 | 49 | |||||
ZQ-90 | 9000 | 0.1 | 75.75 | 123.79 | 15 | 40 | 70 | 3.64 |
0.2 | 87.87 | 145.5 | 44 | |||||
0.3 | 96.96 | 162.73 | 47 | |||||
0.4 | 103.02 | 175.43 | 49 | |||||
ZQ-100 | 10000 | 0.1 | 84.17 | 137.54 | 15 | 40 | 70 | 3.98 |
0.2 | 97.63 | 161.67 | 44 | |||||
0.3 | 107.73 | 180.8 | 47 | |||||
0.4 | 111.1 | 189.19 | 48 | |||||
ZQ-120 | 12000 | 0.1 | 101 | 165.05 | 15 | 40 | 70 | 3.65 |
0.2 | 117.16 | 194.01 | 44 | |||||
0.3 | 129.28 | 216.97 | 47 | |||||
0.4 | 137.36 | 233.91 | 49 |
?
SEMEM_ZQ-20型軸流暖風機用于候車室、體育館等
軸流暖風機安裝安裝與維護:
1、ZQ型軸流暖風機可安裝在墻體結(jié)構(gòu)件上;
2、安裝前應檢查軸流暖風機的完好性;
3、ZQ型軸流暖風機的冷凝水管路上要裝有冷凝水排除器(疏水閥);
4、電動機接線應使風機葉輪按旋轉(zhuǎn)標牌示意方向旋轉(zhuǎn);
5、ZQ型軸流暖風機再使用之前、應仔細檢查各連接處的緊固情況,如有松動,應立即緊固;
6、軸流暖風機每次工作之前,要排凈散熱器中的混合氣體,預熱5-10分鐘再送風工作;
7、軸流暖風機停止工作后,應放凈散熱器中的冷凝水;
8、ZQ型軸流暖風機必須保持清潔,可用壓縮空氣吹除換熱器翅片及其他部位的灰塵;
9、軸流暖風機工作2-3年后,應立即清洗換熱器的水管內(nèi)腔,可用化學方法去除水垢;