消防噴淋泵廠家性能參數(shù)表:
型號(hào) | 口徑 | 流量 | 壓力 | 轉(zhuǎn)速 | 電機(jī)功率 | 效率 | 必需蝕余量 | 重量 |
(L/S) | (MPa)/div> | (r/min) | (kw) | (%) | (M) | Kg | ||
XBD3.2/5-65ISG | 65 | 5 | 0.32 | 2900 | 4 | 63 | 2.5 | 75 |
XBD5/5-65ISG | 65 | 5 | 0.5 | 2900 | 7.5 | 58 | 2.5 | 107 |
XBD8/5-65ISG | 65 | 5 | 0.8 | 2900 | 15 | 50 | 2.5 | 180 |
XBD12.5/5-65ISG | 65 | 5 | 1.25 | 2900 | 30 | 40 | 2.5 | 320 |
XBD3.2/10-80ISG | 80 | 10 | 0.32 | 2900 | 7.5 | 69 | 3 | 105 |
XBD5/10-80ISG | 80 | 10 | 0.5 | 2900 | 15 | 65 | 3 | 175 |
XBD8/10-80ISG | 80 | 10 | 0.8 | 2900 | 22 | 57 | 3 | 240 |
XBD12.5/10-80ISG | 80 | 10 | 1.25 | 2900 | 37 | 54 | 3 | 355 |
XBD3.2/25-100ISG | 100 | 25 | 0.32 | 2900 | 15 | 74 | 4.5 | 191 |
XBD5/25-100ISG | 100 | 25 | 0.5 | 2900 | 22 | 72 | 4 | 245 |
XBD8/25-100ISG | 100 | 25 | 0.8 | 2900 | 37 | 67 | 4 | 345 |
XBD12.5/25-100ISG | 100 | 25 | 1.25 | 2900 | 75 | 66 | 4 | 689 |
XBD3.2/40-125ISG | 125 | 40 | 0.32 | 2900 | 22 | 76 | 4 | 265 |
XBD5/40-125ISG | 125 | 40 | 0.5 | 2900 | 37 | 75 | 5.5 | 395 |
XBD8/40-125ISG | 125 | 40 | 0.8 | 2900 | 55 | 73 | 5 | 580 |
XBD12.5/40-125ISG | 125 | 40 | 1.25 | 2900 | 90 | 70 | 5 | 790 |
XBD3.2/5-150ISG | 150 | 50 | 0.32 | 1480 | 30 | 76 | 3.5 | 410 |
XBD5/50-150ISG | 150 | 50 | 0.5 | 1480 | 45 | 73 | 3.5 | 490 |
XBD3.2/100-200ISG | 200 | 100 | 0.32 | 1480 | 55 | 78 | 3.5 | 417 |
XBD5/100-200ISG | 200 | 100 | 0.5 | 1480 | 75 | 77 | 3.5 | 498 |
消防噴淋泵廠家概述:
消防噴淋泵是對(duì)滿足噴淋系統(tǒng)流量與壓力的泵,當(dāng)發(fā)生火災(zāi)時(shí),噴頭在溫度達(dá)到一定溫度后(一般是68°C,不一樣的噴頭參數(shù)不同)噴頭自動(dòng)爆裂,屋頂消防水箱進(jìn)行火災(zāi)初期的供水(一般情況下水箱滿足噴淋系統(tǒng)10min的供水量),管內(nèi)的水在屋頂消防水箱的作用下自動(dòng)噴出,這時(shí)報(bào)警閥會(huì)因?yàn)閴毫Φ淖兓詣?dòng)打開,水力警鈴響起,壓力開關(guān)自動(dòng)打開,而這個(gè)壓力開關(guān)有根信號(hào)線和XBD消防噴淋泵、消防控制室連鎖,噴淋泵就自動(dòng)啟動(dòng)了。然后消防噴淋泵把水池的水通過管道提供到噴頭,整個(gè)消防系統(tǒng)開始工作。
適用范圍:
消防噴淋泵,供輸送不含固體顆粒的清水及物理化學(xué)性質(zhì)類似于水的液體之用,主要用于消防系統(tǒng)管道增壓送水,也可適用于工業(yè)和城市給排水,高層建筑增壓送水、遠(yuǎn)距離送水、采暖、浴室、鍋爐冷暖水循環(huán)、增壓空調(diào)制冷系統(tǒng)送水及設(shè)備配套等場合。